Ankos 66 Ltd - Aerosol Fire Extingushers, E-mail: info(@)ankos.eu Tel:+359-885-779869; +359-885-021131; Fax: +359-2-8431910



 

 


  AGS-11/1, AGS-11/2, AGS-11/3

  Generator of Fire Extinguishing Aerosol

    Are designed for generating of gaseous-aerosol mixture which stops the process of flame burning when reaches the necessary concentration.
    Generators are made in a shape of a low metal cylinder which has a nozzle gap at the whole circle. Despite its small dimensions these generators have large protected volume:
        AGS 11/1 - up to 2.3 m3
        AGS 11/2 - up to 3.4 m3
        AGS 11/3 - up to 6.0 m3
    Due to its construction, the mass fraction of condensed phase is significantly reduced and the temperature of generator body is reduced as well.
    The electrical impulse which comes to the starter * which is installed inside generators, ignites the aerosol forming cartridge. During the burning of it the fire extinguishing aerosol is produced. The aerosol flow penetrates the cooling layer and comes out of generator through the nozzle.
    Generators are recommended for fire protection of the transport, electronic equipment, high voltage power units, different high-frequency devices including those which are used on the transport (it conforms to requirements of vibration loads on the railroad, motor and air transport).
    Manufacturer guarantees that generators conforms to requirements of technical conditions and GOST if the consumer respects conditions which are indicated in the Instruction Manual.

    The warranty period is 18 months.
    Lifetime – 10 years.
    Operating life – 5 years

    - The starter type is chosen by the Buyer.

 


AGS 11/1

AGS 11/1

AGS 11/2

AGS 11/2

AGS 11/3

AGS 11/3

AGS scheme 11-1

Technical characteristics

  • Fire classes

    AB

    Type AGS
    AGS 11/1
    AGS 11/2
    AGS 11/3

    The mass of aerosol generating cartridge

    0.11 kg

    0.17 kg
    0.3 kg

    Protected volume

    2,2 m3

    3,4 m3
    6,0 m3

    Mass

    0.6 kg

    0.85 kg
    1,2 kg

    Diameter - Height, mm

    122 x 23

    124 x 32
    135 x 52

    Time of operating

    7-8 sec

    9 - 11 sec
    19 - 21 sec

    Aerosol temperature at the distance of 0.5 m from generator

    75°

    Starter

    int. UZ 7.5

    Starter resistance

    7.5 Om

    Starter minimum current

    Starting voltage

    8 – 30 V

    Duration of the starting impulse

    Not less than 1.5 sec

    Delay of generator start up

    < 2 sec

    Operating conditions

    -50° C / + 50° C, humidity up to 98%

Instruction manual

     Download AGS 11/1
     Download AGS 11/2
     Download AGS 11/3

  

   

Aerosol fire fighting
The search of new fire fighting technologies has demanded to use the existing fundamental discoveries and developments in the sphere of volume fire fighting.

Read more >>

 

Automatic fire extinguishing
The fire has always been one of the most frightening and dangerous elements. That is why there have been developed a lot of technologies and devices which reduce the possibility of fire to minimum.

Read more >>

 


СД CEN/TR 15276-1:2009, СД CEN/TR 15276-2:2009

Where to use aerosol fire extingusher generators?

       

Wherehoses

Electricity

servers, computers
cars
     
ships, trains, airplanes
houses
ags-5
ags

Contacts

Commercial department
     +359 885 779-869
     +359 885 021-131
     +359 2 843-19-10 (fax)

Address:
     Sofia, Bulgaria
     Dragovitsa str. 8

Email: info @ ankos.eu
Skype: ankos.eu




Copyright © Ankos 66 Ltd, 2009

Гласувай за тази страница в Българския ТОП