AGS 11/6 -
Generator of Fire Extinguishing Aerosol
Description
AGS-11/6 is designed for generating of gaseous-aerosol mixture which stops the process of flame burning when reaches the necessary concentration.
Generator is made in a shape of a low metal cylinder which has a nozzle gap at the whole circle. Despite its small dimensions this generator has large protected volume up to 48 m3. Due to its construction, the mass fraction of condensed phase is significantly reduced and the temperature of generator body is reduced as well. Has a lot of modifications of mount type and direction of aerosol stream. The basic modifications are given below.
The electrical impulse which comes to the starter * which is installed inside generator, ignites the aerosol forming cartridge. During the burning of it the fire extinguishing aerosol is produced. The aerosol flow penetrates the cooling layer and comes out of generator through the nozzle. Generator is recommended mainly for fire protection of the transport. Due to its constructive features can be used at the energy facilities.
Manufacturer guarantees that generator conforms to requirements of technical conditions and GOST if the consumer respects conditions which are indicated in the Instruction Manual.
The warranty period is 18 months
Lifetime – 10 years
Operating life – 5 years
* The starter type is chosen by the Buyer
Technical characteristics
The mass of aerosol generating cartridge |
2.4 kg |
Protected volume |
48 m3 |
Mass |
4.5 kg |
Diameter - Height |
217 mm x 104 mm |
Time of operating |
40 sec |
Aerosol temperature at the distance of 0.5 m from generator |
100° |
Starter |
UZ-7.5 – internal VR-7.5, VRTH - external |
VEL, VELTH - external |
Starter resistance |
7.5 Om |
2.5-4 Om |
Starter minimum current |
1À |
0,4 À |
Starting voltage |
8 – 30 V |
1,5 – 24 V |
Duration of the starting impulse |
Not less than 1.5 sec |
Not less than 0.1 sec |
Delay of generator start up |
< 1.5 sec |
Operating conditions |
-50° C / + 50° C, humidity up to 98% |
Modifications
|
|
|
Aerosol outflow at A circle 360° |
Aerosol outflow at sector of 150° |
Aerosol outflow at two sectors of 80° each |
AGS-11/6-00 |
AGS-11/6-02 |
AGS-11/6-01 |
Screw starter VEL, VR |
Screw starter VEL, VR |
Screw starter VEL, VR |
AGS-11/6-083
|
AGS-11/5-04 |
AGS-11/6-05 |
Built-in starter UZ-7.5 |
Built-in starter UZ-7.5 |
Built-in starter UZ-7.5 |
Aerosol fire fighting
The search of new fire fighting technologies has demanded to use the existing fundamental discoveries and developments in the sphere of volume fire fighting.
Read more >> |
|
|
|